How do sound absorption classes A–E differ from the αw and NRC ratings?
Sound absorption classes A–E under ISO 11654 rank materials by the weighted sound absorption coefficient αw across the 250 to 4000 Hz bands. The American NRC rating (ASTM C423), by contrast, is a simple arithmetic mean of absorption at 250, 500, 1000 and 2000 Hz. Both parameters help with initial screening, but only the octave-band chart gives a complete picture of a panel's performance.
The European standard ISO 11654 groups construction products into five classes, each assigned a strict αw range (values below 0.15 remain unclassified):
Class A (αw = 0.90–1.00): the highest absorption performance, typical of thick mineral boards, wool panels and PET felt absorbers installed with an air gap.
Class B (αw = 0.80–0.85): high absorption, sufficient for most office spaces given adequate surface coverage.
Class C (αw = 0.60–0.75): moderate absorption, used in zones with lower speech noise loads or on walls as a complement to ceiling treatment.
Class D (αw = 0.30–0.55): basic reverberation correction, typical of thin felt claddings (e.g. 9–12 mm) bonded directly to a hard substrate.
Class E (αw = 0.15–0.25): low absorption, relevant mainly at very high frequencies.
The single-number αw rating is derived by fitting a shifted reference curve to the measured octave-band results. As a result, it can mask a material's weak performance in the low range (125–250 Hz). If a panel shows significantly higher absorption in one range than the αw value alone would suggest, ISO 11654 requires a shape indicator to be added: L (low band, 250 Hz), M (mid band, 500–1000 Hz) or H (high band, 2000–4000 Hz).
In offices, the key band for speech intelligibility is 500–2000 Hz, while the 250–500 Hz band determines voice depth and the sense of boominess in small rooms. Before specifying a product in a design, always check the table or chart of αp values across the full frequency spectrum rather than relying solely on the class letter.
How to match the absorption class to an office zone?
The choice of absorption class depends on the room's function, the number of noise sources and the available mounting surface. In dense open-plan areas and video conferencing rooms, Class A or B systems are the standard, as they reduce reverberation time RT60 to the target 0.4–0.6 s. In circulation and transition zones, Class C absorbers are usually sufficient, eliminating fatiguing reverberation without over-deadening the interior.
Each office zone requires a different approach to acoustic treatment:
Open space: the goal is to limit speech propagation between workstations in line with the ISO 3382-3 methodology (spatial decay rate of speech and distraction distance) and to keep reverberation time RT60 within 0.4–0.6 s, in accordance with good design practice and the requirements of PN-B-02151-4. The first line of defence is acoustic ceiling panels, such as
EcoCloudislands or verticalEcoBaffleunits, supported byEcoScreendesk dividers that block the direct sound path.Conference and video call rooms: the priority is to control early reflections from parallel walls and the table, and to eliminate flutter echo, which degrades signal quality in video conferencing microphones. The best results come from combining a Class A ceiling with wall panels (
EcoWall,EcoTiles) positioned at the participants' head height.Private offices and focus rooms: small volumes with large glazed areas are particularly prone to boominess in the 250–500 Hz bands. They require absorbers that are also effective in the lower speech range, installed on at least two adjacent surfaces (the ceiling plus one or two walls).
Corridors, reception areas and breakout zones: the aim is to reduce harsh reverberation in high lobbies and dampen circulation noise before it travels into the work area. A good solution is integrated acoustic lighting for offices, such as
EcoLampfixtures suspended over the reception desk or an informal meeting area.
Office zone | Recommended class (ISO 11654) | Key bands / acoustic objective | Typical mounting solutions |
Open space | Class A or B (ceiling), C–D (dividers) | 500–2000 Hz; limiting speech propagation (ISO 3382-3), RT60 approx. 0.4–0.6 s |
|
Conference and video call rooms | Class A or B (ceiling and walls) | 250–2000 Hz; eliminating early reflections and flutter echo, clarity for microphones |
|
Private offices and focus rooms | Class A or B | 250–1000 Hz; reducing boominess in small volumes, comfort during phone calls | Ceiling panel mounted with an air gap + |
Corridors, reception areas, breakout zones | Class B or C | 500–4000 Hz; reducing reverberation in circulation areas and high lobbies |
|
Why doesn't Class A on the wall always outperform Class B on the ceiling?
The actual reduction in reverberation time is determined by the room's total equivalent sound absorption area, i.e. the product of the absorption coefficient and the material's effective surface area (A = Σ αi · Si). A large Class B ceiling provides far more absorption than a few small Class A panels hung on a wall. In addition, the air gap above a ceiling absorber significantly enhances absorption of the lower speech frequencies.
Consider a simple example of a 60 m² office. Installing 8 m² of thick Class A panels (αw = 0.95) on a wall adds 7.6 m² of equivalent absorption area to the room. Installing 28 m² of Class B acoustic islands (αw = 0.80) on the ceiling yields 22.4 m² of absorption – an almost threefold greater reduction in reverberation, despite the theoretically lower letter on the data sheet.
The second physical factor is the distance from a hard surface. A sound wave reaches its maximum particle velocity at a distance of one quarter of its wavelength from a wall or ceiling. A thin PET felt panel bonded directly to concrete absorbs energy mainly above 1000 Hz. The same material suspended 150–300 mm below the ceiling slab begins to perform effectively in the 250–500 Hz bands, and when installed as a free-hanging island it absorbs sound on both sides.
At this point, it is essential to clearly distinguish between two separate parameters in building acoustics. Class A panels, regardless of their quantity, only reduce the reverberation time RT60 within a room (absorption αw). They will not improve the sound insulation of the partition between rooms (R'w and DnT,w ratings). If conversations from an adjacent conference room can be heard through a glass partition or poorly sealed door, lining the wall with felt or wool will have negligible effect. Sound transmission problems are solved with heavier partitions, laminated acoustic glass, drop-down door seals and barriers in the ceiling void. When in doubt, the right strategy can be determined through office acoustic design, preceded in existing premises by acoustic and reverberation time measurements.
4 most common mistakes when reading acoustic panel data sheets
Comparing materials solely by their absorption class letter leads to discrepancies between the design and the post-installation result. Data sheets differ in the specimen mounting method used during ISO 354 laboratory testing, the range of frequencies tested and the way results are presented. Eliminating four recurring interpretation errors allows for a reliable comparison of offers and helps avoid costly corrections after office handover.
Comparing results from mounting with an air gap against mounting bonded directly to the wall. ISO 354 test reports specify the specimen mounting type. Type A means direct contact with a hard substrate, while Type E (e.g. E-200) means suspension with a 200 mm air gap. Comparing a panel tested in Type E-200 with a product tested in Type A distorts the comparison, particularly in the 125–500 Hz bands.
Ignoring the 250–500 Hz band. Two panels may have the same Class C or a similar NRC, yet one may have α = 0.45 at 250 Hz and the other only 0.10. In small meeting rooms and private offices, the latter will cause male voices to sound boomy, despite good damping of high-frequency rustling.
Insufficient surface coverage despite purchasing Class A panels. A decorative 3–4 m² composition in a 25 m² conference room will enhance the interior's aesthetics but will only marginally reduce reverberation time. The starting point should always be a calculation of the required absorption area A for the volume and finishes of the specific room.
Confusing the absorption coefficient αw with the sound insulation rating Rw or R'w. The abbreviations look similar, but they describe different physical phenomena. The αw value ranges from 0 to 1 (dimensionless) and indicates the amount of energy absorbed within a room. Rw, R'w and DnT,w are expressed in decibels (dB) and describe the ability of a wall, door or floor to block sound between adjacent rooms.
Frequently Asked Questions (FAQ)
Should offices always use Class A panels?
Not necessarily. Class A is justified where mounting surface is limited (e.g. in rooms with extensive glazing) and in dense open-plan spaces. With a large share of absorptive surface on the ceiling and walls, Class B systems – and Class C in circulation areas – can achieve the required reverberation time RT60 at a lower budget.
How does the αw coefficient differ from the American NRC?
The αw rating (ISO 11654) is determined by fitting a reference curve across the 250–4000 Hz bands, taking into account any increased absorption at low, mid or high frequencies (L, M, H). NRC (ASTM C423) is a simple arithmetic mean of absorption at 250, 500, 1000 and 2000 Hz, rounded to the nearest 0.05. Due to the different calculation methods, the same material may have αw = 0.80 (Class B) and NRC = 0.85 at the same time.
Will Class A acoustic panels block conversations from the room next door?
No. Absorptive panels reduce reverberation and noise levels within the room in which they are installed, but have minimal impact on the sound insulation of partition walls (R'w / DnT,w). To stop conversations from travelling between rooms, you need to increase the partition's sound insulation, seal the doors and close off flanking paths (e.g. the void above a suspended ceiling or shared ventilation ducts).
What percentage of the ceiling or wall area should be covered with panels in an open-plan office?
In a typical open-plan office with a ceiling height of 2.8–3.2 m, a full Class A suspended ceiling usually covers 80–100% of the floor plan. With free-hanging Class A/B acoustic islands, which absorb sound on both sides, effective coverage is typically 40–60% of the ceiling area, supplemented by wall panels or desk dividers along speech propagation paths.
Bibliography and sources
Standards and technical documents
ISO 11654:1997 (PN-EN ISO 11654) – Acoustics — Sound absorbers for use in buildings — Rating of sound absorption (sound absorption classes A–E, the αw rating and shape indicators L, M, H).
ISO 354:2003 (PN-EN ISO 354) – Acoustics — Measurement of sound absorption in a reverberation room (reverberation room measurements and specimen mounting types A and E).
ISO 3382-3:2022 (PN-EN ISO 3382-3) – Acoustics — Measurement of room acoustic parameters — Part 3: Open plan offices (speech propagation and distraction distance parameters in open-plan offices).
PN-B-02151-4:2015-06 – Building acoustics. Protection against noise in buildings. Part 4: Requirements for reverberation conditions and speech intelligibility in rooms and guidelines for testing.
ASTM C423-23 – Standard Test Method for Sound Absorption and Sound Absorption Coefficients by the Reverberation Room Method (methodology for determining the NRC rating).